Copper vs Aluminum Wire: Voltage Drop, Cost & When to Use Each
Copper has about 61% lower resistance than aluminum at the same wire gauge, resulting in less voltage drop for the same current and distance. However, aluminum is lighter and less expensive per ampere of capacity. For equivalent performance, aluminum conductors typically need to be two AWG sizes larger than copper. The choice between materials depends on the application, budget, and installation requirements.
Copper vs Aluminum Conductivity
The electrical properties of copper and aluminum make each material suitable for different applications. Understanding these fundamental differences helps explain why copper is preferred for some installations while aluminum dominates others.
Electrical Conductivity
Copper is one of the best electrical conductors among common metals, second only to silver. At 20°C, copper has a conductivity of approximately 59.6 MS/m (megasiemens per meter). Aluminum's conductivity is about 37.7 MS/m—roughly 63% that of copper. This means aluminum requires a larger cross-sectional area to carry the same current with equivalent resistance.
The conductivity difference translates directly to voltage drop. For the same wire size (AWG), length, and current, aluminum will have approximately 1.6 times the voltage drop of copper. This is why aluminum conductors must be larger than copper to achieve comparable performance.
Weight Comparison
While copper conducts better, aluminum is significantly lighter. Copper weighs about 8.96 g/cm³, while aluminum weighs only 2.70 g/cm³—about 30% of copper's weight. Even when using larger aluminum conductors to match copper's ampacity, the aluminum installation is typically lighter.
For example, 4/0 AWG copper weighs approximately 640 pounds per 1000 feet, while 250 kcmil aluminum (roughly equivalent in ampacity) weighs about 230 pounds per 1000 feet. This weight difference matters for overhead lines, long conduit runs, and applications where structural support is a concern.
Thermal Properties
Both materials expand when heated, but at different rates. Aluminum has a higher coefficient of thermal expansion than copper, meaning it expands and contracts more with temperature changes. This characteristic requires special consideration at terminations and connections to prevent loosening over time.
Aluminum also has different thermal conductivity than copper, affecting how quickly heat dissipates from the conductor. These thermal properties influence how each material performs under varying load conditions and ambient temperatures.
Resistance Comparison Table
The following table compares resistance values for copper and aluminum conductors of the same AWG size. Values are from NEC Chapter 9, Table 8 at 75°C.
| Wire Size (AWG) | Copper (Ω/kft) | Aluminum (Ω/kft) | Aluminum/Copper Ratio |
|---|---|---|---|
| 14 | 3.14 | 5.17 | 1.65× |
| 12 | 1.98 | 3.25 | 1.64× |
| 10 | 1.24 | 2.04 | 1.65× |
| 8 | 0.778 | 1.28 | 1.64× |
| 6 | 0.491 | 0.808 | 1.65× |
| 4 | 0.308 | 0.508 | 1.65× |
| 2 | 0.194 | 0.319 | 1.64× |
| 1 | 0.154 | 0.253 | 1.64× |
| 1/0 | 0.122 | 0.201 | 1.65× |
| 2/0 | 0.0967 | 0.159 | 1.64× |
| 3/0 | 0.0766 | 0.126 | 1.64× |
| 4/0 | 0.0608 | 0.100 | 1.64× |
As the table shows, aluminum consistently has about 1.64-1.65 times the resistance of copper at every wire size. This ratio remains constant across the AWG range, making it straightforward to compare voltage drop between the two materials for any application.
When to Use Copper
Copper is the preferred choice in several key situations where its superior conductivity and connection reliability outweigh its higher cost.
Branch Circuits
For typical residential and commercial branch circuits (15A and 20A), copper is the standard choice. The wire sizes involved (14 AWG and 12 AWG) are small enough that cost difference is minimal, and copper's easier termination makes it more practical for the many connections in branch circuit wiring. Most device terminals in receptacles and switches are designed for copper.
Space-Constrained Installations
When conduit space is limited, copper's smaller size for equivalent ampacity becomes valuable. Using copper may mean the difference between fitting conductors in existing conduit versus replacing with larger conduit—a significant cost and labor consideration in retrofit work.
Wet or Corrosive Environments
Copper resists corrosion better than aluminum in most environments. In wet locations, coastal areas with salt exposure, or industrial settings with corrosive atmospheres, copper's durability makes it the safer choice. While aluminum can be used with proper terminations and anti-oxidant compound, copper requires less maintenance attention in challenging environments.
Frequent Termination Changes
In applications where connections are frequently made and remade—such as temporary installations, equipment that's regularly moved, or training facilities—copper's easier termination and greater tolerance for handling makes it preferable. Aluminum connections require more care and proper techniques that may not always be followed during quick changes.
Motor Leads and Flexible Connections
For flexible cord, motor leads, and applications requiring frequent flexing, copper is essentially mandatory. Aluminum wire is more prone to fatigue failure when flexed repeatedly. All portable cord and flexible cable standards specify copper conductors.
When to Use Aluminum
Aluminum is the economical choice for many larger installations where its cost advantages outweigh the need for larger conductors and careful termination practices.
Service Entrance Conductors
The conductors between the utility meter and main panel carry the entire building load and are often the largest conductors in an installation. For 100A, 200A, and larger services, aluminum provides substantial cost savings. Most utility meters and main breaker panels have terminals rated for aluminum, making this application straightforward.
Feeders to Subpanels
Feeders to detached buildings, subpanels, and other major distribution points carry significant current over distances where conductor cost becomes meaningful. A 100-foot run of 2/0 AWG aluminum for a garage subpanel costs significantly less than the equivalent 1/0 AWG copper, with minimal difference in voltage drop when properly sized.
Industrial and Commercial Feeders
Large commercial and industrial buildings routinely use aluminum for major feeders. The cost savings on 500 kcmil aluminum versus 350 kcmil copper (roughly equivalent ampacity) multiplied across thousands of feet of feeder runs represents substantial budget savings. Professional electricians in these settings are trained in proper aluminum termination techniques.
Overhead Service Drops
Utility service drops from the pole to the building almost universally use aluminum because of its lighter weight. The reduced weight means longer spans between supports and less strain on attachment points. This application is so dominated by aluminum that copper service drops are rare.
Large Motor Circuits
For larger motors (typically 50 HP and above) with long runs, aluminum feeders provide good value. The larger conduit required for aluminum may be offset by conductor cost savings, especially when the conduit size increases only marginally. Many industrial motor control centers have terminals designed for aluminum conductors.
Cost Comparison
Understanding the true cost comparison between copper and aluminum requires considering not just wire price, but also the larger conduit sometimes needed for aluminum and installation labor differences.
Raw Conductor Cost
The following table shows approximate relative costs for copper and aluminum conductors of equivalent ampacity (prices vary significantly over time based on commodity markets):
| Copper Size | Equivalent Aluminum | Copper Cost (relative) | Aluminum Cost (relative) | Savings with Aluminum |
|---|---|---|---|---|
| 6 AWG (55A) | 4 AWG (55A) | 1.00 | 0.50 | 50% |
| 4 AWG (70A) | 2 AWG (75A) | 1.00 | 0.45 | 55% |
| 2 AWG (95A) | 1/0 AWG (100A) | 1.00 | 0.40 | 60% |
| 1/0 AWG (125A) | 3/0 AWG (130A) | 1.00 | 0.35 | 65% |
| 4/0 AWG (195A) | 250 kcmil (205A) | 1.00 | 0.30 | 70% |
Note: These are representative ratios. Actual prices fluctuate with copper and aluminum commodity markets. The savings with aluminum generally increase with larger wire sizes.
Total Installed Cost
When comparing total installed cost, consider:
- Conduit cost: Aluminum may require larger conduit due to bigger wire size
- Labor time: Aluminum terminations take more care and time
- Anti-oxidant compound: Required for aluminum connections
- Terminal compatibility: Some equipment requires copper or CU/AL rated terminals
For short runs with many terminations, copper may actually be less expensive overall. For long runs with few terminations, aluminum typically provides significant savings even accounting for larger conduit.
Installation Considerations
Proper installation techniques differ between copper and aluminum, with aluminum requiring more attention to detail at connections.
Aluminum Connection Requirements
Aluminum connections require specific practices to ensure long-term reliability:
- Use only AL or CU/AL rated terminals: Terminals not rated for aluminum will fail over time
- Apply anti-oxidant compound: Also called oxide inhibitor or joint compound, this prevents the oxide layer that forms on aluminum from increasing connection resistance
- Follow torque specifications: Use a calibrated torque wrench to achieve proper connection pressure
- Consider compression fittings: For splices and terminations, compression connectors rated for aluminum provide reliable connections
Why Aluminum Connections Can Fail
Aluminum presents several challenges at terminations. First, aluminum oxidizes quickly when exposed to air, forming a thin aluminum oxide layer that has high resistance. Second, aluminum expands and contracts more than copper with temperature changes, which can loosen connections over time. Third, aluminum is softer than copper and can creep (slowly deform) under sustained pressure, also loosening connections.
These issues led to problems with aluminum wiring in homes during the 1960s and 1970s, when improper terminations caused connection failures and fires. Modern aluminum conductors use different alloys (AA-8000 series) with better properties, and proper termination practices make aluminum safe and reliable when installed correctly.
Copper Connection Advantages
Copper connections are more forgiving of less-than-perfect installation practices. Copper forms a thin oxide layer that's still conductive, unlike aluminum oxide. Copper has lower thermal expansion and doesn't creep, so connections remain tight over time. Standard terminals without special ratings work fine with copper. While proper torque is still important, copper connections have more margin for error.
Mixing Copper and Aluminum
When copper and aluminum conductors must be connected together, special precautions are needed. Direct copper-to-aluminum connections can cause galvanic corrosion, especially in the presence of moisture. Use only connectors specifically rated for copper-to-aluminum connections, or use a transition splice that keeps the two metals from direct contact. Never splice copper and aluminum using standard wire nuts or twist-on connectors not rated for this purpose.
Equivalent Wire Sizes
The following table shows copper and aluminum wire sizes that provide approximately equivalent ampacity and performance. Use these equivalents when substituting one material for the other.
| Copper AWG | Equivalent Aluminum AWG | Ampacity (75°C) | Notes |
|---|---|---|---|
| 12 | 10 | 25-30A | Minimum for 20A circuits |
| 10 | 8 | 35-40A | 30A circuits |
| 8 | 6 | 50A | Range, dryer, large AC |
| 6 | 4 | 65A | Subpanels, large circuits |
| 4 | 2 | 85-90A | Subpanels, feeders |
| 3 | 1 | 100A | 100A service/feeders |
| 2 | 1/0 | 115-120A | Small commercial feeders |
| 1 | 2/0 | 130-135A | Commercial feeders |
| 1/0 | 3/0 | 150-155A | 150A residential service |
| 2/0 | 4/0 | 175-180A | 175A service |
| 3/0 | 250 kcmil | 200-205A | 200A service |
| 4/0 | 300 kcmil | 230A | Large residential |
The two-size difference (e.g., 6 AWG copper ≈ 4 AWG aluminum) is a general rule that applies across most of the AWG range. For voltage drop calculations, remember that the equivalent aluminum will have slightly different resistance, so always use the actual resistance values from NEC Table 8 rather than assuming equivalence. Use our voltage drop calculator to compare specific scenarios with either material.
Compare Voltage Drop for Copper vs Aluminum
Use our free calculator to see exact voltage drop with either conductor material.
Open CalculatorFrequently Asked Questions
Yes, modern aluminum wiring is safe when properly installed with appropriate terminals and techniques. The problems that gave aluminum a bad reputation occurred in the 1960s-70s with improper terminations on devices not rated for aluminum. Today's aluminum conductors use improved AA-8000 series alloys, and proper installation practices are well established. Aluminum is the standard choice for service entrances and large feeders.
For equivalent ampacity, aluminum conductors need to be approximately two AWG sizes larger than copper. For example, where 6 AWG copper is needed, 4 AWG aluminum provides similar current-carrying capacity. This relationship holds fairly consistently across the wire size range. For equivalent voltage drop at the same current, the sizing is similar since the larger aluminum has correspondingly lower resistance.
Yes, but only using connectors specifically rated for copper-to-aluminum (CU/AL) connections. These connectors are designed to prevent galvanic corrosion and accommodate the different expansion rates of the two metals. Never use standard wire nuts or connectors not rated for this purpose. Split-bolt connectors, properly rated crimp connectors, and certain mechanical lugs are available for copper-to-aluminum connections.
Aluminum oxidizes rapidly when exposed to air, forming aluminum oxide on the surface. Unlike copper oxide, which is still somewhat conductive, aluminum oxide is an insulator. This oxide layer can increase connection resistance, causing heat buildup and eventual failure. Anti-oxidant compound (oxide inhibitor) penetrates and displaces the oxide layer, ensuring good metal-to-metal contact. It also prevents new oxide from forming on the connection.
For long runs with high current, aluminum is often the better choice economically. The cost savings on conductor material typically outweighs the slightly larger conduit needed. Both materials can achieve the same voltage drop performance—aluminum just requires larger wire to do so. Use the voltage drop calculator to compare specific scenarios. For short runs with many connections, copper may be more practical due to easier termination.